The installation and deployment of equipotential bonding connectors must comply with relevant industry standards, such as GB 50057 and IEC 62305. Prior to installation, environmental conditions, the status of the grounding system, and the requirements of the equipment to be connected should be evaluated. Maintenance tasks include periodic inspection of connection integrity and testing for electrical continuity.
1. Installation dimensions: Hole spacing of 120 mm.
2. This product is connected in series between the equipment ground wire and the lightning protection ground wire.
3. There is no specific directional requirement for the series connection of the equipotential bonding connector; the conductor cross-section should be ≥10 mm², and the wire length should be kept as short as possible.
During installation, ensure that connecting wires are short and straight to minimize inductance; in corrosive environments, select corrosion-resistant materials or implement protective measures; specific requirements may apply to different industries (e.g., healthcare, rail transit), so relevant standards should be consulted.
4. This product is generally designed to be maintenance-free; however, to ensure long-term reliability, it is recommended to periodically check connection tightness and inspect for any visual abnormalities, as well as to conduct and record electrical tests. The operating status of the equipotential bonding connector should be promptly inspected and recorded following thunderstorms.